A1 / 0F

Fujitsu Air Conditioner

Severity: Moderate

What it means

On Fujitsu's wired remote controls, A1 and 0F are the discharge temperature error.
The discharge is the hot gas leaving the compressor, and this error usually means it runs too hot.
The checklist in Fujitsu General America's service help center: switch the power off at the disconnect for 5 minutes, which should reset the code.
If it stays, a technician measures the discharge thermistor, then the running pressures with gauges.
Pressures well below normal mean the system is likely low on refrigerant or has a leak.
Fujitsu's service bulletin 0039 adds a known cause on the AOU36RLXFZH and AOU45RLXFZ multi-zone outdoor units: the flare nuts on unused ports can work loose in shipping and leak.
Fujitsu's fix is to recover and reweigh the refrigerant, and to replace the outdoor control board if the error stays.

Affected Models

  • Fujitsu air conditioners with a wired remote control (UTY-RNBYU, UTY-RNNUM, UTY-RVNUM, UTY-RSNUM, UTY-DMMUM, UTY-RSRY, UTY-RNRUZ)

How to Fix It

  1. Switch the system off at the outdoor disconnect for 5 minutes, then back on.

  2. Code back?
    Call a licensed HVAC technician.
    Leak testing and refrigerant work need a licence.