d7

Gree Air Conditioner

Severity: Minor

What it means

Gree's service manuals for its GMV VRF systems list d7 as a humidity sensor error of an indoor unit.
The indoor board reports it when the sensor's reading stays outside its limits for 5 seconds.
The reasons Gree gives are a poor contact between the humidity sensor and its terminal on the main board, a faulty sensor, or a fault in the detecting circuit.
GMV systems are Gree's VRF air conditioning: one outdoor unit serving many indoor units, mostly in offices, shops and larger homes.
d7 is not on Gree's US code list for its home split air conditioners.

Affected Models

  • Gree GMV5 and GMV5E DC inverter VRF systems
  • Gree Ultra Heating GMV5 Multi VRF (North America)

How to Fix It

  1. Note the code and which indoor unit shows it, and contact the installer or Gree service.

    The sensor and its plug are inside the indoor unit, which a technician opens.