H9

Gree Air Conditioner

Severity:

What it means

Gree's code table for its GMV5E VRF systems lists H9 as desynchronizing protection of the inverter fan, shown on the outdoor unit's main board.
It means the outdoor fan's motor doesn't follow the drive that turns it.
The reasons Gree gives are a poor contact of the fan's motor wires, a broken fan, a blade that is blocked or a rusty motor shaft, or a faulty fan drive board.
The manual's own section on H9 is headed inverter compressor, but every cause in it is about the fan, as in the table.
GMV systems are Gree's VRF air conditioning: one outdoor unit serving many indoor units, mostly in offices, shops and larger homes.

Affected Models

  • Gree GMV5 and GMV5E DC inverter VRF systems

How to Fix It

  1. Look at the outdoor unit from outside, without reaching in: if leaves, ice or a cover block the fan, switch the system off at the breaker before anything is cleared.

  2. Contact the installer or Gree service.

    The motor wires and the drive board are inside the outdoor unit, on high voltage.