U6
Gree Air Conditioner
Severity: ModerateWhat it means
Gree's service manual for its GMV5E VRF systems lists U6 as an alarm because a valve is abnormal.
It belongs to the commissioning codes, so it normally shows while the system is being set up and tested.
The system reads its pressures and concludes that a cut-off valve on the outdoor unit is not open.
GMV systems are Gree's VRF air conditioning: one outdoor unit serving many indoor units, mostly in offices, shops and larger homes.
U6 is not on Gree's US code list for its home split air conditioners.
Affected Models
- Gree GMV5 and GMV5E DC inverter VRF systems
How to Fix It
-
Contact the installer.
The manual's fix is to check again that the outdoor unit's cut-off valves are open, then confirm on the main board.
The valves are part of the sealed refrigerant circuit, so leave them to a technician.