UNDERVOLTAGE (1900 codes)
Generac Standby Generator
Severity:What it means
Generac's support article says UNDERVOLTAGE means the generator is not producing proper voltage, from a long period of low voltage or a sudden loss of voltage.
The article gives codes 1900 to 1906, with a red light, on Next Generation 10-28 kW and Guardian 10-26 kW (2017 to present) air-cooled generators.
Generac says it is often linked to fuel supply or fuel selection, the circuitry, firmware or voltage production, and usually needs a dealer.
How to Fix It
-
On a Guardian generator, check that the controller is set to the fuel you actually use (natural gas or LP), and that the fuel jets are in the matching position.
On Next Generation generators, the installer sets the fuel in the Field Pro app.
-
Clear the alarm.
Evolution controller: press OFF, ENTER twice, then AUTO.
Power Zone 200 controller: hold the OFF button for 3 seconds. -
Restart the generator with no load connected.
Generac says never to start a generator while it is under load.
-
If the alarm comes back, contact a Generac authorized service dealer.
Generac says the electrical side of this fault usually needs a dealer's diagnosis.