SHUTDOWN SWITCH (2800 / 2801)
Generac Standby Generator
Severity: ModerateWhat it means
Generac's support article says error code 2800 or 2801 means one or more auxiliary shutdown switches are activated, or in the open (OFF) position.
The message may read STOPPED - ALARM / ERROR CODE 2800 or SHUTDOWN SWITCH (2800), and a flashing red light may come with it.
A switch may have been turned off on purpose during service, or knocked by accident.
On Next Generation generators, 2801 can mean the second emergency shutdown switch near the transfer switch.
How to Fix It
-
Make sure the generator is safe to run and that nobody turned the switch off for service or an emergency.
-
Find the shutdown switches.
Guardian: small black rubber-coated switches, one on the back of the generator, and on some two-cylinder models a second one inside the housing near the control panel.
Next Generation: a factory-installed switch (see the owner's manual), and on some installs a second switch near the automatic transfer switch. -
Set each switch to I (ON/CLOSED).
On a Guardian, press the I side of the switch.
If there are two switches, both must be ON before the alarm will clear. -
Clear the alarm, then return to AUTO.
Guardian (Evolution controller): press the red OFF button, press ENTER twice, then press the green AUTO button.
Next Generation (Power Zone 200): hold OFF for about 3 seconds, then press AUTO. -
If the code comes back without anyone touching a switch, contact a Generac authorized service dealer.
When to Call a Professional
Generac warns never to bypass, disconnect or modify an auxiliary shutdown switch to stop the error: these switches are safety devices.
Frequently Asked Questions
What about 50 Hz generators?
Generac says some 50 Hz models use an emergency stop button on the side, near the status lights.
On the pull-to-reset type, pull the button out, then follow the owner's manual to clear the alarm.