OVERSPEED (1200, 1205, 1208)
Generac Standby Generator
Severity:What it means
The engine turned too fast, and the generator shut itself down.
Power Zone 410: 1200 is more than 72 Hz for 3 seconds, and 1205 is more than 75 Hz for 1 second.
1208 is a frequency more than 20% off its target for 5 seconds.
Generac gives a broken stepper wire as a possible cause of 1205.
Affected Models
- Generac liquid-cooled standby generators with the Power Zone 410 controller
- Generac 15 to 50 kW Protector diesel generators with the Evolution controller
- Generac 10 to 24 kW air-cooled home standby generators with the Evolution controller
How to Fix It
-
Leave the generator in OFF.
-
Contact a Generac authorized service dealer.
All of Generac's owner's manuals we read give this one answer for OVERSPEED.