Low Fuel Level (2680), Extremely Low Fuel Level (2681)
Generac Standby Generator
Severity: ModerateWhat it means
These are for diesel generators.
Low Fuel Level (2680), or Low Fuel (20%) on the Evolution controller, is a warning: about 20% of the fuel is left, and the generator keeps running.
Extremely Low Fuel Level (2681), or Low Fuel (10%), is an alarm: less than 10% is left, and the generator shuts down.
Affected Models
- Generac liquid-cooled standby generators with the Power Zone 410 controller
- Generac 15 to 50 kW Protector diesel generators with the Evolution controller
How to Fix It
-
Fill the tank with diesel.
Stop below 90%: above that the controller warns Diesel High Fuel Level (2682).
-
Clear the alarm.
Evolution controller: press OFF, then ENTER.
Power Zone 410: on the Alarm Screen press STOP, then ENTER. -
Set the generator back to AUTO.
Frequently Asked Questions
What is Critical High Fuel Level (2691)?
The fuel is above the level set as the high limit, 95% from the factory, for more than one second.