Low Oil Level (2735), High Oil Temperature (2725)

Generac Standby Generator

Severity:

What it means

Low Oil Level (2735): the oil was below its limit 60 seconds after the start.
High Oil Temperature (2725): the oil was hotter than 320 °F (160 °C) while the engine ran.
Both are alarms that stop the generator.

Affected Models

  • Generac liquid-cooled standby generators with the Power Zone 410 controller

How to Fix It

  1. Let the engine cool, and check the oil on the dipstick.

  2. Add oil of the grade the manual gives, and look for leaks.

  3. 2725: make sure nothing blocks the air inlet and outlet.

  4. Clear the alarm.

    Power Zone 410: on the Alarm Screen press STOP, then ENTER.

  5. If it returns, contact a dealer.