b2, b3

Gree Air Conditioner

Severity: Moderate

What it means

Gree's service manual for its GMV5E VRF systems lists b2 as defrost temperature sensor 1 and b3 as defrost temperature sensor 2.
Gree's Ultra Heating GMV5 manual calls b3 the sensor at the outlet of the outdoor coil.
The outdoor board uses these sensors to tell when the outdoor coil needs defrosting in heating mode.
The outdoor board reports it when the sensor's reading stays outside its limits for 30 seconds.
The reasons Gree gives are a poor contact between the sensor and its terminal on the main board, a faulty sensor, or a fault in the detecting circuit.
GMV systems are Gree's VRF air conditioning: one outdoor unit serving many indoor units, mostly in offices, shops and larger homes.
Neither code is on Gree's US code list for its home split air conditioners.

Affected Models

  • Gree GMV5 and GMV5E DC inverter VRF systems
  • Gree Ultra Heating GMV5 Multi VRF (b3)
  • Gree U-Match ducted split air conditioners (b2)

How to Fix It

  1. Note the code and contact the installer or Gree service.

    Checking the sensor's plug, the sensor and the outdoor board is work for a VRF technician.