b4

Gree Air Conditioner

Severity: Moderate

What it means

Gree's service manual for its GMV5E VRF systems lists b4 as a malfunction of the liquid temperature sensor of the sub-cooler.
The sub-cooler is a small heat exchanger in the outdoor unit that cools the liquid refrigerant before it goes to the indoor units.
The outdoor board reports it when the sensor's reading stays outside its limits for 30 seconds.
The reasons Gree gives are a poor contact between the sensor and its terminal on the main board, a faulty sensor, or a fault in the detecting circuit.
In the same table b5 is the sub-cooler's gas temperature sensor, while on Gree's home multi-zone units b5 is a liquid pipe sensor.
GMV systems are Gree's VRF air conditioning: one outdoor unit serving many indoor units, mostly in offices, shops and larger homes.
b4 is not on Gree's US code list for its home split air conditioners.

Affected Models

  • Gree GMV5 and GMV5E DC inverter VRF systems

How to Fix It

  1. Note the code and contact the installer or Gree service.

    Checking the sensor's plug, the sensor and the outdoor board is work for a VRF technician.