BATTERY PROBLEM (2760)
Generac Standby Generator
Severity: ModerateWhat it means
The battery is above 16 volts, or it still takes more than 600 mA at the end of an 18-hour charge.
Generac's Power Zone 410 manual says: this indicates battery may be bad.
It is a warning with a yellow light, so the generator can still run.
Affected Models
- Generac liquid-cooled standby generators with the Power Zone 410 controller
- Generac 15 to 50 kW Protector diesel generators with the Evolution controller
- Generac 10 to 24 kW air-cooled home standby generators with the Evolution controller
How to Fix It
-
Look up the battery's age, and check that its clamps are clean and tight.
-
Open the BATTERY menu on the controller.
If it says Check Battery, replace the battery.
-
If it says Good, contact a Generac authorized service dealer.