BATTERY PROBLEM (2760)

Generac Standby Generator

Severity: Moderate

What it means

The battery is above 16 volts, or it still takes more than 600 mA at the end of an 18-hour charge.
Generac's Power Zone 410 manual says: this indicates battery may be bad.
It is a warning with a yellow light, so the generator can still run.

Affected Models

  • Generac liquid-cooled standby generators with the Power Zone 410 controller
  • Generac 15 to 50 kW Protector diesel generators with the Evolution controller
  • Generac 10 to 24 kW air-cooled home standby generators with the Evolution controller

How to Fix It

  1. Look up the battery's age, and check that its clamps are clean and tight.

  2. Open the BATTERY menu on the controller.

    If it says Check Battery, replace the battery.

  3. If it says Good, contact a Generac authorized service dealer.