Very Low Battery (2751)
Generac Standby Generator
Severity:What it means
The battery was below 9.0 volts for 60 seconds.
Unlike Low Battery (2750, below 12.1 volts for a minute), this one is an alarm: the generator won't run.
Affected Models
- Generac liquid-cooled standby generators with the Power Zone 410 controller
How to Fix It
-
Check that the battery clamps are tight and not corroded.
-
Check the breaker that feeds the battery charger.
Without AC the charger shows Charger Missing AC (2780).
-
Have the battery tested, and replace it if it doesn't hold a charge.
-
Clear the alarm.
Power Zone 410: on the Alarm Screen press STOP, then ENTER.