FS, deF
Hayward Pool Heat Pump
Severity: MinorWhat it means
FS (Summit) or deF (HeatPro) means the heat pump is in defrost mode. Hayward says this is normal when the outdoor temperature is in the low to mid 50s°F (about 10 to 13°C) or below.
When the coil gets down to 29°F (-2°C), the compressor stops and the fan keeps running. A Summit shows FS until the coil reaches 42°F (6°C), then restarts.
A HeatPro runs the fan for up to three 15-minute cycles, showing only the water temperature. If the coil is still below 50°F (10°C) after the third cycle, it shuts down for 2 hours and shows deF.
How to Fix It
-
Leave it alone: the compressor restarts by itself once the coil has warmed up.
-
Check the coil for severe frost. If the heat pump keeps cycling on and off with a badly frosted coil, Hayward's owner's manual says to turn it off to protect the compressor.
-
If FS or deF shows when it is warmer than the mid 50s°F outside, the defrost sensor may be failing. Call for service to have it tested.