LP, LP3
Hayward Pool Heat Pump
Severity: ModerateWhat it means
LP means the low pressure switch is open. Hayward's troubleshooting guide says it opens when the refrigerant pressure drops below 80 PSI, and resets by itself at 120 PSI.
The most common cause is a refrigerant leak. Long spells below 21°F (-6°C) outside also cause LP, and the switch closes by itself once it warms above 40°F (4°C).
On Summit heat pumps, LP3 shows after three LP faults and the heat pump shuts down. If the heat pump's own time clock runs the pool pump, the pump stops too.
How to Fix It
-
If it is very cold outside, wait for warmer weather and see whether the code clears.
-
Check that nothing blocks the air flow around the heat pump, and that its coil is clean.
-
Otherwise, call for service. Hayward's Summit manual says to call for service if LP or LP3 occurs. A leak has to be found and repaired and the system recharged, and a bad fan motor or capacitor can also cause an LP that comes and goes. The refrigerant system and its pressure switches are a job for a qualified heat pump technician.
Frequently Asked Questions
My newer HeatPro shows E02, not LP. Is it the same?
On newer HeatPro models such as the HP31005T, E02 is low pressure protection. Hayward's fix is to check the pressure switch and refrigerant circuit, which is a technician job.