FAULT- CHECK IGN CONTROL, FAULT- CHECK IGNITION STEPS

Jandy Pool Heater

Severity: Critical

What it means

FAULT- CHECK IGN CONTROL on a Jandy JXi or LXi gas heater means a fault in the ignition sequence. The 2014 Pro Series JXi manual calls it FAULT- CHECK IGNITION STEPS.
Jandy's causes: air pressure switch tubing that is broken, split, pinched or disconnected; a fan that is not running or runs slow; restricted air flow at the intake or the exhaust; a broken igniter; low gas supply pressure; or no flame at the burner. The LXi manual adds oscillating pump pressure.

Affected Models

  • Jandy JXi gas pool and spa heaters
  • Jandy LXi gas pool and spa heaters

How to Fix It

  1. Make sure the gas supply to the heater is on. On propane, check that the tank is not empty.

  2. Check that nothing blocks the air intake or the exhaust outlet. An enclosed heater needs the clearances and the room ventilation its manual asks for.

  3. Clean the filter. It is on the remedy list in both the 2014 JXi and the LXi manual, and the LXi manual ties it to oscillating pump pressure.

  4. Everything else is for a qualified service technician: the air pressure switch tubing, the fan, the igniter, the gas pressure and supply pipe, and the wiring of the igniter, gas valve and ignition control.

    Jandy says the heater must be serviced only by a qualified professional service technician: the work involves fuel gas, electricity and safety controls.

Frequently Asked Questions

What do the flashes on the ignition control mean?

The ignition control inside the heater has an LED that the technician reads alongside the fault message.
Steady light: ignition control fault. One flash: air flow fault. Two flashes: there is a flame when there is no call for heat. Three flashes: ignition lockout, after three tries to light (a soft lockout).